Control any motor
and you only have to get to know, and use, one series of inverters
Functional safety included
from compact devices to modular multi-axis systems with single-axis and double-axis modules
Rapid, straightforward commissioning
as the electronic rating plate supplies all the gear unit and motor data
Everything falls into place in our new MOVI-C® modular automation system – the engineering software matches the control and inverter technology and everything comes together seamlessly with the drive technology.
Tell us what you need and we will offer you a customized, future-proof automation solution.
A digital data cable makes the motor an active part of your data network, providing all motor data – such as encoder data, temperature data, commissioning data, and data from other sensors – to the application inverter and the connected networks at any time. This information can be used to capture detailed operational data and compile maintenance forecasts. As the type designations, serial numbers and logistics data associated with motors are identified and supplied automatically, an inventory of all the drives in a plant can be compiled automatically at the touch of a button. Repairs, exchanges and enhancements can be tracked and traced at any time.
Integrated into the inverter technology
Due to the requirements laid down in technical standards and the drive to have humans and machines working hand in hand, the number of plant areas equipped with functional safety technology is constantly growing. As a result, functional safety is an integral part of any application.
By introducing MOVISAFE® CS..A safety cards, SEW EURODRIVE has made functional safety an integral element of all MOVI C® application inverters. Even the basic unit in the MOVIDRIVE® series features STO in PL e. All higher-level safety functions are achieved by inserting an option card, including all the necessary connections to the inverter technology – encoder, communication and STO. This helps you reduce costs to only what is necessary to achieve the functions you actually need.
Functions in the basic unit
MOVISAFE® safety card functions
Hardware | MOVISAFE® CSB21A | MOVISAFE® CSB31A | MOVISAFE® CSS21A | MOVISAFE® CSS31A | MOVISAFE® CSA31A |
Safe inputs | 4 | 4 | 4 | 4 | 4 |
Safe outputs | - | 2 | 2 | 2 | 2 |
Safe stop function | STO, SS1c | STO, SS1c, SBC | STO, SS1c, SBC | STO, SS1c, SBC | STO, SS1c, SBC, SBT |
Safe motion function | - | - | SOS, SS1b, SS2, SLS, SSR, SLA, SSM | SOS, SS1b, SS2, SLS, SSR, SLA, SSM | SOS, SS1b, SS2, SLS, SSR, SLA, SSM |
Safe positioning function | - | - | SLI, SDI | SLI, SDI | SLI, SDI, SCA, SLP |
Safe communication | PROFIsafe, FSoE | PROFIsafe, FSoE | PROFIsafe, FSoE | PROFIsafe, FSoE | PROFIsafe, FSoE |
Additional multi-encoder input | - | Yes | - | Yes | Yes |
Compact multi-axis system comprising power supply modules, regenerative power supply modules, and single-axis and double-axis modules
Single-axis application frequency inverter with its own power supply connection:
Single-axis application frequency inverter with its own power supply connection and direct fieldbus connection via plug-in fieldbus interfaces. In addition to the features of MOVIDRIVE® system, MOVIDRIVE® technology offers:
MOVIDRIVE® modular | MOVIDRIVE® system | MOVIDRIVE® technology | |
Nominal Voltage V | 3 x AC 380 – 500 | 3 x AC 200 – 240 3 x AC 380 – 500 | |
Rated output – power supply module kW | 10 - 110 | - | |
Rated output, regenerative power supply module, block-shaped kW | 50 - 75 | - | |
Rated output current – single-axis module kW | - | 0.55 – 315 | |
Rated output current, single-axis module A | 2 - 180 | - | |
Rated output current, double-axis module A | 2 - 8 | ||
Overload capacity | 250 % | 200 % | |
Overview of options | Multi-encoder input in the basic unit, encoder option for additional EtherCAT® encoder interface, extension for inputs and outputs, regenerative power supply, braking resistors, line choke, line filter, output chokes, output filter |